Fire Pumps
Fire pump set (Electric/Diesel + Jockey) — illustrative
Project & Commissioning Support

Fire Pumps (Electric / Diesel + Jockey)

Fire pump sets provide the design flow and pressure continuously to the fire main. Configured in line with local codes and the principles of NFPA 20 / EN 12845, they are available as end-suction, split-case or vertical turbine, with electric and/or diesel drive, a jockey (pressure-maintenance) pump and a smart controller.

Selection Guide: Right Pump Type & Drive

Choose by required design flow (Q), head (H), suction conditions (NPSH), water source and reliability needs.

Scenario Recommendation Typical Range Note
Compact plant / medium flow End-suction + Jockey 500–1000 gpm, 6–10 bar Economical, easy maintenance
High flow / long mains Split-case (double suction) 1000–2500 gpm, 8–12 bar High efficiency, low vibration
Groundwater / deep well Vertical turbine Project-specific For variable water level sources
Power outage risk Electric + Diesel standby Diesel as back-up Often mandated for continuity
Pressure fluctuation Jockey pump 3–15 m³/h, 6–12 bar Maintains line pressure

Technical Specifications & Components

Values are typical and may vary by brand/model. Use the product data sheet and hydraulic calculations for exact sizing.

Item End-Suction Split-Case Vertical Turbine Notes
Flow (Q) ~500–1200 gpm ~1000–3000 gpm Project-specific Match to system demand
Head (H) 6–10 bar 8–12 bar Wide range Depends on sprinkler/hydrant design
Drive Electric Electric / Diesel Electric / Diesel Diesel improves reliability
Control Pressure switch / controller PLC/panel + alarms PLC/panel + sensors Auto/manual start logic
Key components Check + OS&Y, by-pass Test line + flowmeter Suction strainer/column Relief, drain, vibration pads
Pump room layout / test line — illustrative

Commissioning & Checklist

Installation Notes

  • Keep suction short/straight and air-tight (NPSH).
  • Valve lineup: OS&Y, check valve, by-pass and relief in proper order.
  • Isolate base with vibration pads and flexible connectors.
  • Verify performance via test line and flowmeter.

Start-Up Steps

  • Verify electric/diesel start scenarios.
  • Calibrate pressure switches and jockey settings.
  • Record performance curve at nominal flow.
  • Test alarms: fault, low fuel, low pressure, etc.

Maintenance & Periodic Tests

Regular testing and service are critical for reliability. Intervals below are general guidance—follow site procedures and regulations first.

Interval Action Description
Weekly Automatic test run Verify flow/pressure and alarm logs
Monthly Visual + leak check Suction/discharge flanges, vibration & noise
6 months Functional test & calibration Pressure switches, electrical values, flowmeter
Yearly Performance test Q-H verification, bearings/oil/cooling
For diesel Fuel–battery–cooling Fuel aging, battery charge, belt tension

Frequently Asked Questions

Is Electric + Diesel mandatory?

It depends on continuity needs and outage risk. Many industrial specs mandate a standby diesel for reliability.

What does the jockey pump do?

It keeps line pressure stable and prevents unnecessary starts of main pumps due to minor leaks.

Why are a test line and flowmeter needed?

To measure Q-H performance against the pump curve during commissioning and periodic verification.